The following specifications apply to G2R Relays mounted in a G70R-SOC08 Relay Terminal and not the G2R Relay itself.
Relay Terminal
更新日期 2017年4月10日
The following specifications apply to G2R Relays mounted in a G70R-SOC08 Relay Terminal and not the G2R Relay itself.
Rated voltage | 24 V DC |
---|---|
Rated current | 25.8 mA |
Coil resistance | 1,100 Ω |
Must-operate voltage | 70% max. of rated voltage |
Must release voltage | 15% min. of rated voltage |
Max. voltage | 130% of rated voltage |
Power consumption | Approx. 530 mW |
Load | Resistive load (cosφ = 1) | |
---|---|---|
Rated load | 10 A at 250 V AC, 10 A at 30 V DC | |
Rated carry current | 10 A | |
Max. switching voltage | 380 V AC, 125 V DC | |
Max. switching current | 10 A | |
Max. switching capacity
(reference value) |
2,500 VA, 300 W | |
Min. permissible load
(reference value) * |
10 mA at 5 V DC | |
Endurance | Electrical | 100,000 operations min. (under and at the rated load at 1,800 operations/h) |
Mechanical | 10,000,000 operations min. (at 18,000 operations/h) |
* This value is for a switching frequency of 120 times per minute.
Model | G70R-SOC08 | |
---|---|---|
Classification | Relay outputs | |
Contact configuration | 8 points (SPST-NO × 8) | |
Contact structure | Single | |
Contact resistance *1 | 30 mΩ max. | |
Must-operate time *2 | 15 ms max. | |
Release time *2 | 15 ms max. | |
Max. switching
frequency |
Mechanical | 18,000 operations/h |
Rated load | 1,800 operations/h | |
Insulation resistance | 100 MΩ min. (at 500 V DC) | |
Dielectric
strength |
Between coil and contact | 2,000 V AC for 1 min between coil and contact |
Between contacts of same
polarity |
750 V AC for 1 min | |
Between contacts of different
polarity |
1,500 V AC for 1 min | |
Vibration
resistance |
Destruction | 10 to 55 to 10 Hz, 0.5-mm amplitude (1.0-mm double) |
Malfunction | 10 to 55 to 10 Hz, 0.5-mm amplitude (1.0-mm double) | |
Shock
resistance |
Destruction | 300 m/s2 |
Malfunction | 100 m/s2 | |
Noise
immunity |
Power input (normal mode) | 600 V for 10 min with a pulse width of 100 ns to 1 μs |
Power input (common mode) | 1.5 kV for 10 min with a pulse width of 100 ns to 1 μs | |
Input cable (coiling) | 1.5 kV for 10 min with a pulse width of 100 ns to 1 μs | |
Unit body (coiling) | 600 V for 10 min with a pulse width of 100 ns to 1 μs | |
Operating voltage range | 24 V DC +10%/-15% | |
Current consumption *3 | Approx. 185 mA at 24 V DC | |
Cable length | Between block and controller | 5 m max. (reference value for AWG24) |
Between block and external
device |
Determine appropriate length for the connected load. | |
LED indicator color | Orange | |
Coil surge absorber | Diode | |
Ambient operating temperature | -10 to 55°C | |
Ambient storage temperature | 35% to 85% | |
Ambient operating humidity | -20 to 65°C | |
Mounting strength | No damage when 49 N pull load was applied for 1 s in all directions
(except for 9.8 N in direction of rail) |
|
Terminal
strength |
Tightening torque | 9.8 N·m |
Pull strength | 49 N for 1 min | |
Weight | Approx. 350 g |
Note: These values are initial values.
*1. Measurement: 1 A at 5 V DC
*2. Ambient temperature: 23°C
*3. The current consumption is the value when all points are ON and includes the G2R Relay coil current.
更新日期 2017年4月10日